server rack china smart rack china difference between hot aisle and cold aisle containment cold aisle containment supplier data center cold aisle containment curtains small wall mount server rack Textbook for Operation and Maintenance Engineer of Power and Environment Specialty of Data Center - Resistance and Resistance Law

Textbook for Operation and Maintenance Engineer of Power and Environment Specialty of Data Center - Composition of complex DC circuit server rack China

Server Rack Network Rack Network Cabinet Wall mounted Cabinet Open Rack Rack Accessories Rack Tray Blank Plate Gasket Wire Mesh Cable Tray Grid Cable Tray Basket Cable Tray Perforated Cable Tray Cable Ladder

Solution: In the first step, assume that the branch current flowing through R1 is I1, R2 is I2, and R3 is I3, as shown in Figure 1.2-5 (b).
Step 2: List the node equation
I1 + I2 - I3 = 0 for node a
For node b, there is - I1 - I2 + I3 = 0
Or I3 = I1+I2
Step 3: List the loop voltage equation
Loop 1: E1 = I1R1 + I3R3
Loop 2: E2 = I2R2 + I3R3
Step 4: Substitute I3 = I1 + I2 into the above equation, and then substitute the parameters in the figure to solve the simultaneous equation
30=3I1+4(I1+I2)
50=4I2+4(I1+I2)
Simplified 7I1 + 4I2 = 30
4I1 + 8I2 = 50, I1 = 1A
I2=5.75A
I3=I1+I2=6.75A
Step 5: Verify the solution results, and use three branches to calculate Uab
Branch ① Uab = E1 - I1R1 = 30 - 1 × 3=27(V)
Branch ② Uab = E2 - I2R2 = 50 - 5.75 × 4=27(V)
Branch ③ Uab = I3R3 = 6.75 × 4=27(V)
The calculated results are the same, indicating that the calculated results are correct.Intelligent micro module data room server rack network rack network cabinet wall mounted cabinet open rack rack accessories rack tray blank plate gasket wire mesh cable tray basket cable tray perforated cable tray cable ladder PDU

Server Rack Network Rack Network Cabinet Wall mounted Cabinet Open Rack Rack Accessories Rack Tray Blank Plate Gasket Wire Mesh Cable Tray Grid Cable Tray Basket Cable Tray Perforated Cable Tray Cable Ladder data center cold aisle cold aisle containment curtains  data center cold aisle containment hot aisle cold aisle data center design smart server rack hot cold aisle containment systems hot aisle cold aisle

Intelligent micro module data room server rack network rack network cabinet wall mounted cabinet open rack rack accessories rack tray blank plate gasket wire mesh cable tray basket cable tray perforated cable tray cable ladder PDU

It can be seen from the above formula that if the current flowing into the node is specified as "+", the current flowing out of the node is specified as "-"

 Cable Tray Cable Ladder subzero cold aisle containment cold aisle containment system hot cold aisle data center cold aisle china containment price hot aisle containment vs cold aisle containment intelligent data center magazine what is intelligent data center  canovate smart server rack  emerson smart server rack server rack network rack Network cabinet wall mounted cabinet Open Racks Frame rack accessories rack tray blank panel spacer

Cable Tray Cable Ladder subzero cold aisle containment cold aisle containment system hot cold aisle data center cold aisle china containment price hot aisle containment vs cold aisle containment intelligent data center magazine what is intelligent data center  canovate smart server rack  emerson smart server rack server rack network rack Network cabinet wall mounted cabinet Open Racks Frame rack accessories rack tray blank panel spacer

For any node in the circuit, the algebraic sum of the current flowing into (or out of) the node is equal to zero. This is Kirchhoff's first law.

1.2.3.2 Kirchhoff's second law (loop voltage law)Server Rack Network Rack Network Cabinet Wall mounted Cabinet Open Rack Rack Accessories Rack Tray Blank Plate Gasket Wire Mesh Cable Tray Grid Cable Tray Basket Cable Tray Perforated Cable Tray Cable Ladder subzero cold aisle containment cold aisle containment system hot cold aisle data center cold aisle china containment price hot aisle containment vs cold aisle containment intelligent data center magazine what is intelligent data center  canovate smart server rack  emerson smart server rack server rack network rack Network cabinet wall mounted cabinet Open Racks Frame rack accessories rack tray blank panel spacer

A circuit composed of many branches is called a network, and any closed path in the network is called a loop. In a closed circuit, if it makes a detour in any direction, the algebra of all electromotive forces in the circuit is Σ E must be equal to all electricity in the circuit

Algebraic sum of resistive voltage drop Σ IR, the expression is:Σ E= Σ IR or Σ E= Σ U The electromotive force and voltage drop that are the same as the bypass direction are specified as positive values, and - 5 the electromotive force and voltage drop that are opposite to the bypass direction are specified as negative values. As shown in Figure 1.2-4, E1 - E2 in loop 1=I1R1 - I2R2, while E1 in loop 2=I1R1 + I3R3.cold aisle containment cold aisle containment system hot cold aisle data center cold aisle china containment price hot aisle containment vs cold aisle containment intelligent data center magazine what is intelligent data center  canovate smart server rack  emerson smart server rack server rack network rack Network cabinet wall mounted cabinet Open Racks Frame rack accessories rack tray blank panel spacer

Textbook for Operation and Maintenance Engineer of Power and Environment Specialty of Data Center - Calculation of Complex DC Circuitserver rack China