Requirements for spacing between cabinet columns

Update:19-09-2024
Summary:

The spacing arrangement of cabinet rows should be compr […]

The spacing arrangement of cabinet rows should be comprehensively determined based on the size of the operating space, cable direction, cabinet heat dissipation, cabinet power supply, management and other requirements, and should comply with the following regulations:

 

1.When the cabinets are facing each other, the distance between the fronts of the cabinets should not be less than 1300mm, and the distance between the backs of the cabinets and the distance between the last row of cabinets and the wall should not be less than 1000mm;

2.When the cabinets are arranged in the same direction, the distance between the front of the cabinets and the distance between the first row of cabinets and the wall should not be less than 1100mm, and the distance between the last row of cabinets and the wall should not be less than 1000mm;

3.Cabinets and equipment in the modified or expanded data center should be reasonably arranged according to the original power supply method and equipment power consumption. When this cannot be met, aisle spacing should meet safety requirements.

 

 The width of the walkway between the side of the cabinet and the wall should not be less than 1000mm; the width of the walkway between two parallel rows of cabinets should not be less than 1500mm.