Delta connection of generator winding in micro-module cold channel data center

Update:22-02-2023
Summary:

When the generator winding is connected in a symmetrica […]

When the generator winding is connected in a symmetrical triangle, as shown in Figure 1-4-11, the end X of the first phase is connected with the start B of the second phase, the end Y of the second phase is connected with the start C of the third phase, and the end Z of the third phase is connected with the start A of the first phase. Three terminal wires are led out from three contacts. It is obvious from Figure 1-4-11 that the line voltage is equal to the phase voltage when connecting.
UAB=UA UBC=UB UCA=UC, that is, U line=U phase
When the three-phase generator is connected in triangle as shown in Fig. 1-4-11, the circuit formed is A-XB-XC-Z, as shown in Fig
1-4-12 can be seen. Because the vector sum of EA and EB is equal to the vector of EC and the direction is opposite, the total vector sum of electric potential is equal to zero.
If it is not connected as shown in Figure 1-4-11, even if the external circuit is not connected to the load, in the closed circuit, due to the small impedance of the winding, a considerable current will be generated, which will cause the generator winding to burn out.
As shown in Figure 1-4-13, the phase C is wrongly connected, then the resultant potential in the winding closed circuit (Figure 1-4-14) will
It can be seen that the potential acting on the circuit is twice that of one phase.
Because the potential of three-phase generator is usually not a real sine wave, the vector sum of three-phase potential in the winding closed circuit cannot be zero, so the triangular connection of generator winding is rarely seen, and is usually connected into a star. In star connection, even if the winding is wrongly connected, it will not cause the accident of burning the generator. Of course, this situation is still not allowed for load power supply.