The average illumination of the working lighting in the […]
The average illumination of the working lighting in the computer room is greater than or equal to 500Lux; the principle of ensuring that there is no "dead zone" between the lamp sources 0.8M off the ground is implemented. The lamp tube adopts energy-saving fluorescent tubes, and the lamp switches are grouped and centrally controlled. At the same time, emergency lighting with batteries is installed to facilitate lighting after a power outage in the city.
Emergency lighting ensures emergency treatment for personnel and can safely and quickly evacuate along the passageway to the exit or emergency exit. The illuminance is greater than 50LUX, and UPS is used to supply power to some lamps, and the glare limit level is required to reach Level I.
The lighting fixtures in the computer room use 600mm×600mm lighting fixtures.
1. In general lighting design, indicators such as uniformity, stability, color rendering of light sources, glare and shadows of computer rooms should also be carefully considered. The overall computer room design generally uses a color temperature of 3300K, which is the color closest to sunlight. Even if the staff work in the computer room for a long time, their eyes will not feel tired. The original lighting in the computer room was renovated according to the cabinet layout, and the lighting was arranged directly above the sightseeing walkway and the column walkway.
2. Emergency lighting Emergency lighting, also known as accident lighting, is the lighting provided when normal lighting is malfunctioned or power outage is extinguished according to the requirements of the bidding documents: the channel is to the exit or emergency exit, the illuminance is greater than 50LUX, and other parts refer to the relevant standards. The measured illuminance at 0.8 meters above the ground in the middle of the main room and the recorded media storage room shall not be less than 10LUX.
The overall computer room design is: the big data cloud computer room, basic workroom, auxiliary workroom and office are not less than 10% of the specified illuminance; the mechanical and electrical room is not less than 50% of the specified illuminance; the stairs and exit indicator lights are 100%.