When designing a date center room load-bearing, if you want to comply with the computer room specifications, you must consider making a hash load-bearing bracket under the cabinet and double the contact area of the bottom surface of the load-bearing bracket to achieve dispersed floor load-bearing. When the weight of cabinets, air conditioners, UPS and other equipment exceeds the floor load, in order to ensure the safety of the building itself and the earthquake resistance requirements of the general computer room, you need to make a load-bearing dispersed rack for the cabinets, air conditioners, UPS battery cabinets and precision air conditioners. The dispersed load-bearing bracket can disperse the load-bearing capacity of the floor to meet the design value requirements of the floor floor bearing capacity.
The load-bearing dispersed rack of the computer room is generally reinforced with steel beams, which are added according to the location of the equipment. For example, channel steel and angle steel are supported on the load-bearing structure beams (walls) at both ends. For example, add two horizontally penetrated 50*5 angle steel or 10# channel steel to the machine column position, and the load bearing capacity of this column can reach 16,000~18,000N.