Data center cabinet requirements

Update:18-09-2024
Summary:

1.The cabinets of the data center should be selected ac […]

1.The cabinets of the data center should be selected according to the size of servers, storage devices and communication network equipment.

2.The cabinet structure should comply with the following requirements:

  1. The cabinet should be a four-column or six-column cube frame structure;
  2. The horizontal support of the cabinet should be stable and reliable, and can be fixedly installed on the ground according to earthquake-proof requirements;
  3. The side door of the cabinet should be removable;
  4. The cabinet combination should meet the ventilation and heat dissipation requirements after installation.

3.The size of the cabinet is determined according to the usage requirements, and should comply with the requirements in the following table.

Height (h) Width (w) Depth (1) Remarks
2200 800 1100

Suitable for air conditioners using downward air supply.

2200 800 1000

Suitable for air conditioners using upward air supply.

2200 600 1100

Suitable for air conditioners using downward air supply.

2200 600 1000

Suitable for air conditioners using upward air supply.

4. When there are multiple rows of cabinets, the cabinet arrangement should comply with one of the following regulations:

  1. Uniform cabinet orientation;
  2.  Face to face or back to back.

5.When the calorific value is relatively large, appropriate sealing measures should be taken for the cabinet based on the hot and cold aisles.