1.The cabinets of the data center should be selected ac […]
1.The cabinets of the data center should be selected according to the size of servers, storage devices and communication network equipment.
2.The cabinet structure should comply with the following requirements:
3.The size of the cabinet is determined according to the usage requirements, and should comply with the requirements in the following table.
Height (h) | Width (w) | Depth (1) | Remarks |
2200 | 800 | 1100 |
Suitable for air conditioners using downward air supply. |
2200 | 800 | 1000 |
Suitable for air conditioners using upward air supply. |
2200 | 600 | 1100 |
Suitable for air conditioners using downward air supply. |
2200 | 600 | 1000 |
Suitable for air conditioners using upward air supply. |
4. When there are multiple rows of cabinets, the cabinet arrangement should comply with one of the following regulations:
5.When the calorific value is relatively large, appropriate sealing measures should be taken for the cabinet based on the hot and cold aisles.